Parameters

■ Applicable standards:

IEC60298: AC metal-enclosed switchgear and control equipment with rated voltages from 1kV to 52kV.

IEC60694: High-voltage switchgear standard common clauses.

GB3906: 3-35kV AC metal-enclosed switchgear.

GB / T11022: General technical requirements for high voltage switchgear.

GB1984: AC high voltage circuit breaker.

Product feature

P / V-12 is a metal-armored removable switchgear developed with reference to international advanced technology. It is suitable for single buses and its segmented system with three-phase AC, rated voltage of 3 ~ 10kV, and rated frequency of 50Hz, and as receiving and distributing electric energy indoor complete set of distribution equipment. In addition to having the same structure, technical parameters and manufacturing technology as similar international products, it also increases the net clearance of air insulation according to the actual situation of domestic operation. It is currently the highest-grade armored switchgear in China and has reached the international advanced level.

The switchgear combines new vacuum arc extinguishing and mature epoxy insulation technology, and through type test verification, it has been optimized for safety, reliability, economy and efficiency. The products are mainly used in utility, industrial, transportation and power distribution solutions, and also cover many high-demand application areas, such as data centers, oil and gas, mines, and ships. The width 550 mm width double-layer structure design cabinets are more suitable for the application of space-constrained projects such as commercial real estate, data centers, and field reconstruction.

■ The basic skeleton is made of imported high-quality aluminum-zinc coated steel plate and then bolted together. It adopts special processes such as multiple bending and bossing, and is processed by a CNC flexible production processing line. The parts have high dimensional accuracy and structural modeling beautiful, solid and reliable, and because the aluminum-zinc steel plate does not need to be coated, it is not easy to rust. Therefore, the continuity of the skeleton is good, which can ensure that the installed electrical components maintain their excellent electrical and mechanical properties;

■ Circuit breakers use high-quality imported or domestic vacuum circuit breakers (or vacuum contactors). These products have superior performance and reliable operation;

■ The circuit breaker is installed in the "center" manner, and its weight is borne by the side wall of the switchgear, which avoids the impact of the floor on the contact plug and the interchangeability of the handcart. In addition, the precise dimensions of the skeleton manufacture and the contact plug intact rate and handcart swap rate reach 100%;

■ The switchgear is operated and maintained on the front side, with a large window area and high definition. It can clearly display the circuit breaker position indication, opening and closing status indication, and the energy storage status indication of the spring operating mechanism. And safe, convenient operation and maintenance;

■ High protection level. Full consideration has been given to the safety protection requirements for operating personnel. Its enclosure protection level is IP4X, and the door is sealed with rubber; the window is covered with special high-strength glass; the cable room, bus bar room, and circuit breaker room have independent pressure relief channels. Once the internal failure occurs and the pressure rises, the pressure relief channel immediately opens to release the pressure. The sealed structure provides reliable protection for the operating personnel to ensure that the accident cannot spread. Personnel will not be harmed;

■ The "five-proof" interlock of the switchgear is a set of mechanical chain with advanced design and reliable performance, which can reliably prevent misoperation and meet the requirements of Chinese national standards;

■ It considers the importance of insulation strength to operational safety. All designs are evaluated according to the most stringent insulation requirements (higher than IEC standards and meet GB3906 and DL404 standards), and type tests of insulation strength have been performed according to the above standards.

■ Main parameters of switchgear (single layer):

Item

Unit

Parameter

Rated voltage

kV

3.6 7.2 12

Rated insulation level

1min power frequency withstand voltage

kV

25 32 42

Lightning impulse withstand voltage (full wave)

kV

40 60 75

Rated frequency

Hz

50

Rated current of main bus

A

630, 1250, 1600, 2000, 2500, 3150, 4000 *

Branch bus rated current

A

630, 1250, 1600, 2000, 2500, 3150, 4000 *

4s rated thermal stable current (effective value)

kA

25, 31.5, 40, 50

Rated dynamic and stable current (peak)

kA

63, 80, 100, 125

Protection class

 

Enclosure IP4X, circuit breaker room door open IP2X

■ Main parameters of switchgear (double layer):

Item

Unit

Parameter

Rated voltage

kV

12

Rated frequency

Hz

50

Rated insulation level

Power frequency withstand voltage (1 minute)

kV

42

Lightning impulse withstand voltage (peak)

kV

75

Rated current of main bus

A

1250A / 3150A

Rated short-time withstand current

kV

31.5

Rated short time tolerance time

S

4

Rated peak withstand current

kV

80

Protection class

Switchgear enclosure

 

IP41

Between switchgear compartments

 

IP2X

 

Scan the QR code to read on your phone
We could not find any corresponding parameters, please add them to the properties table
Previous
Postcode: 201401
Address: 720 Yuandong Road, Fengxian District, Shanghai
icon

Copyright Shanghai INFRASWIN Energy Co., Ltd. © 2019 All Rights Reserved.   by:300.cn